Main Technical & Charateristic:
The installation altitude of power thansformer should not be over 1000m
Ambient Temperature should be between -40degree centigrade ~ +40 degree centigrade
Hight short-circuit resistant ability
Low loss
Low partial discharge
Low noise
High mechnical strength
No leakage
Easy installation
Maintenance free
Parameters in table:
Model | Voltage combination | Rated Capacity (KVA) | Connection Symbol | No-load loss (kw) | On-load loss(kw) 75 | No-load Current % | Shirt-circuit Impedance % | |
HV(kV) | LV (kv) | |||||||
S9-800/35 | 35±2X2.5% 35±5% | 3.15 6.3 10.5 | 800 | Yd11 | 1.23 | 9.9 | 0.9 | 6.5 |
S9-1000/35 | 1000 | 1.44 | 12.1 | 0.9 | 6.5 | |||
S9-1250/35 | 1250 | 1.76 | 14.6 | 0.81 | 6.5 | |||
S9-1600/35 | 1600 | 2.21 | 17.5 | 0.76 | 6.5 | |||
S9-2000/35 | 2000 | 2.16 | 17.8 | 0.67 | 6.5 | |||
S9-2500/35 | 2500 | 3.15 | 20.7 | 0.67 | 6.5 | |||
S9-3150/35 | 35±5% 38.5±.5% | 3150 | 3.8 | 24.3 | 0.63 | 7.0 | ||
S9-4000/35 | 4000 | 4.25 | 28.8 | 0.63 | 7.0 | |||
S9-5000/35 | 5000 | 5.4 | 33.0 | 0.54 | 7.0 | |||
S9-6300/35 | 35±2X2.5% 38.5±2X2.5% | 11 10.5 6.6 6.3 3.3 3.15 | 6300 | Ynd11 | 6.56 | 36.9 | 0.54 | 7.5 |
S9-8000/35 | 8000 | 9.0 | 40.5 | 0.49 | 7.5 | |||
SF9-10000/35 | 10000 | 10.6 | 47.5 | 0.49 | 7.5 | |||
SF9-12500/35 | 12500 | 12.6 | 56.7 | 0.45 | 8.0 | |||
SF9-16000/35 | 16000 | 15.0 | 69.3 | 0.45 | 8.0 | |||
SF9-20000/35 | 20000 | 18.0 | 83.7 | 0.45 | 8.0 | |||
SF9-25000/35 | 25000 | 21.28 | 99.0 | 0.36 | 8.0 | |||
SF9-31500/35 | 31500 | 25.28 | 118.8 | 0.36 | 8.0 | |||
SF9-40000/35 | 40000 | 28.8 | 155.25 | 0.48 | 8.0 | |||
Note: we can design and manufacture specia6.3l transformer as customers' requirements. Ordering Instruction: 1.product model; 2.rated capacity; 3.voltage range; 4.regulation range; 5.frequency; 6.connection symbol; 7. technical requirements for special transformer. | ||||||||
See more products from this supplier.